For an APC SmartSlot, look up the UPS model in Schneider Electric’s card chart. For Eaton, start with NETWORK-M3 for a supported Mini-Slot UPS or INDGW-X2 for a supported X-Slot UPS. Buy only after the manufacturer’s compatibility list confirms the card for your UPS model and slot. APC compatibility chart · Eaton Mini-Slot specifications · Eaton X-Slot specifications
UPS network card compatibility matrix
| Slot | Card model | Example UPS matches | What to check |
|---|---|---|---|
| APC SmartSlot | AP9640, AP9641, AP9643 (NMC3) | Smart-UPS model prefixes include SMT, SMX, and SRT. | For SUA, check for a manufacture date after 2008 and firmware v1.4.2 or later. For Symmetra PX 250/500, the chart specifies AP9643 only. APC chart |
| APC SmartSlot | AP9544 (NMC3) | Listed single-phase Easy UPS On-Line models include the SRV1KA. | The SRV1KA requires the alternate bracket supplied with the card. Check the chart for the other models that require it. APC chart |
| Eaton Mini-Slot | NETWORK-M3 | 5P, 5PX, 5PX G2, 5SC Rack, and 9PX are among the listed models. | For 93PS, Eaton specifies firmware 2.50 or later. NETWORK-M3 specifications |
| Eaton X-Slot | INDGW-X2 | BladeUPS, 9155, 9355, and 9395 are among the listed models. | Look under Hardware compatibility for your UPS and UPS slot type for X-Slot. INDGW-X2 specifications |
Verify your UPS before ordering
- Copy the full UPS model and check its expansion slot. Schneider Electric lists both SmartSlot and a SmartConnect Ethernet port on the SMT1500RM2UC. Use SmartSlot for the card lookup. SMT1500RM2UC specifications
- Match the UPS to the card’s exact model number. For SMT1500RM2UC, match the SMT prefix in Schneider Electric’s AP9640, AP9641, and AP9643 row. For an Eaton 9355, find 9355 under Hardware compatibility on the INDGW-X2 page. APC chart · INDGW-X2 specifications
- Check any firmware or bracket conditions, then check what ships with your UPS. Read the notes on the matched row before ordering. Eaton’s 9PX3000RTN specifications list a Mini-Slot and an included NETWORK-M3. APC chart · NETWORK-M3 specifications · 9PX3000RTN specifications
Look up older Eaton card names
Eaton identifies NETWORK-M3 as the upgrade from NETWORK-M2. If you are replacing an M2, confirm the UPS model on the M3 hardware compatibility list. Eaton Gigabit Network Card specifications
For a discontinued ConnectUPS-X Web/SNMP card, Eaton’s legacy lookup lists the Power Xpert Gateway X-Slot UPS card as the replacement. Confirm the UPS model against the specifications for the card you plan to buy. Eaton legacy product lookup
Evidence and limits. Schneider Electric’s NMC compatibility chart and Eaton’s NETWORK-M3 and INDGW-X2 specifications were checked on November 26, 2026. Verification was limited to manufacturer documentation.